EN IEC 60534-2-1:2011

Control valve flow coefficient

Required Kv and Cv to pass a given flow across a given pressure drop, with the choked-flow limit. A live demo of the open-source sizing library.

Service conditions · clause 6

m³/h
bar
bar
Choked-flow check (optional)

Clause 7. A liquid chokes when the vena-contracta pressure reaches the vapour pressure. Supply all three and sizing uses the choked pressure drop, so the valve is not oversized.

bar a
bar a

Required coefficient

Kv
17.68
Cv
20.44
Choked check not performed
Kv = Q / √(Δp / SG)  ·